PowerValue 11 RT – UPS Systems | ABB

BrandABB
11 People watching this product now!
Category:
Description

PowerValue 11 RT G2 The single-phase UPS for critical applications

ABBƒ??s PowerValue11RT G2 is a double-conversion online UPS that guarantees up to10 kVA of clean, reliable power for your critical single-phase applications. As well as maintaining power to your servers, point-of-sale terminals, workstation clusters, routers, switches, hubs and sensitive electronic equipment, the PowerValue11RT G2 also conditions incoming power to eliminate spikes, swells, sags, noise and harmonics.

The PowerValue11RT G2 can be used as a standalone UPS device or installed into a standard 19″rack configuration, with connectivity options available for each. Three units of the 6 or 10kVA models can be configured in parallel to provide redundancy or to increase the systems total capacity up to 30 kW. All units can be fitted with up to four battery modules to extend runtime.

PowerValue 11 RT G2 technical specifications

General data

UPS frame rated power

1 / 2 / 3 / 6 / 10 kVA

UPS module rated power

–

UPS output rated PF

Up to 1.0

Max no of parallel frames

Up to 3 units (model dependent)

Max no of parallel modules across frames

–

Max system power

30 kW

Wiring

1-ph + N + PE

UPS type

Rack or tower convertible

Topology

Online double conversion

Input

Nominal input voltage

208, 220, 230, 240 VAC

Voltage range

120-300 VAC (1-3 kVA)
100-276 VAC (6-10 kVA)

Frequency range

45 – 55 Hz for 50 Hz systems
54 – 66 Hz for 60 Hz systems
40-70 Hz with load 60% (6-10 kVA))

Current THD at 100% load

5% (1-3 kVA)
3% (6-10 kVA)

Power Factor at 100% load

ƒ? 0.995

Output

Rated output voltage (load dependent)

208, 220, 230, 240 VAC

Voltage THD (with linear load)

2% (1-3 kVA)
1% (6-10 kVA)

Rated frequency

50 or 60 Hz (selectable)

Efficiency

Double conversion

Up to 92% (1-3 kVA)
Up to 95% (6-10 kVA)

Eco-mode

95% (1 – 3 kVA)
98% (6 – 10 kVA)

Communications

User interface

LCD

Communication ports

USB, RS-232, SNMP slot, potential-free contacts

Software

Monitoring and shutdown software available as option