Vertiv Liebert GXT5-1500IRT5UXLE UPS, 1500 VA / 1500 W, Graphic LCD, On-line (VFI) Mode, Integrated Batteries, 50 or 60Hz Frequency, Energy Star 2.0 Certified, Black | GXT5-1500IRT2UXLE

Original price was: د.إ 4,524.67.Current price is: د.إ 3,619.72.

BrandVertiv
ModelGXT5-1500IRT2UXLE
20 People watching this product now!
SKU: GTC51915 Category:
Description

GXT5-1000IRT5UXLE

Liebert™ GXT5 UPS is an online double conversion UPS solution which offers premium power outage protection and continuous power conditioning in a compact and flexible deployment system. It protects critical equipment from all power disturbances due to blackouts, brownouts, saps, surges or noise interference.

 

– Capability for parallel/redundant operation (10kVA)
– Integrated batteries and easy to install, configure and operate
– New RDU101 SNMP/webcard with advanced features
– Compatibility with environmental sensors
– Integrated dry-contacts and configurable definition
– DCIM compatible: Power Insight
– Energy Star® 2.0 certified
– Programmable output sockets for optimum battery usage

Rating

Power Rating

  • 1500 VA / 1500 W

Dimensions (D×W×H)

Unit

  • 400 x 430 x 85

Weight (kg)

Unit

  • 16.5

Input AC

Input Voltage

     – 230 VAC

Frequency

  • 40Hz ~ 70Hz; Auto Sensing

Input Power Cord

  • C14

Output AC

Output Voltage

  • 200/208/220/230/240 VAC

Output Receptacles

  • C13×8

Waveform

  • Sine wave

Utility(AC) Model Overload

  • >200% for 250ms; 150- 200% for 2 seconds; 125- 150% for 50 seconds; 105-125% 60 seconds;

 

Internal Charger

Charging current

  • Nominal 2.2 A; Maximum 8 A

Battery

Type

  • Valve-regulated, non-spillable, lead acid

Qty×V×Rating

  • 3 × 12V × 9.0Ah

Recharge Time

  • 3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal Batteries
    Only)

Environmental Requirements

Operating Temperature,°F (°C)

  • +32 to +122 (0 to 50); Operating temperature may be increased to 122°F (50°C with a 10% de-rating of
    the output power

Storage Temperature, °F(°C)

  • 4to +140 (-20 to 60)( contain batteries will be from 15 to 40°C.)

Relative Humidity

  • 0% to 95%, non-condensing

Operating Elevation

  • Up to 10,000 ft. (3000m) at 77ºF (25ºC) without derating

Audible Noise

  • <46dBA max @ 3ft. (1m) front and sides <43dBA max @ 3ft. (1m) rear

Agency

Safety

  • EN 62040-1:2008+A1:2013;
    GS mark;
    UL 1778 5th Edition and CSA 22.2 No. 107.1

EMC

  • EN 62040-2:2006
    EN 61000-3-2:2014
    EN 61000-3-3:2013

Transportation

  • ISTA Procedure 1A

Surge Immunity

  • ANSI C62.41 Category B IEC 61000-4-5 Surges/Lightning

RFI/EMI

  • CISPR22 Class A